Click or drag to resize

eClxMotorState Enumeration

Enum to define the CLX and DIN Motor States.

Namespace: Crestron.SimplSharpPro.Lighting
Assembly: Crestron.SimplSharpPro.Lighting (in Crestron.SimplSharpPro.Lighting.dll) Version: 2.21.121
Syntax
C#
public enum eClxMotorState
Members
Member nameValueDescription
Open0 The motor will move in the open direction: Until it reaches the mechanical limit; or Set motor to Stop state to abort the operation anytime; or When the period given by the "ParameterMaximumTime" parameter has expired
Close1 The motor will move in the close direction: Until it reaches the mechanical limit; or Set motor to Stop state to abort the operation anytime; or When the period given by the "ParameterMaximumTime" parameter has expired
JogOpen2 Jogs the motor in the open direction: Until when the period given by the "ParameterJogTime" parameter has expired; or Set motor to Stop state to abort the operation anytime
JogClose3 Jogs the motor in the close direction: Until when the period given by the "ParameterJogTime" parameter has expired; or Set motor to Stop state to abort the operation anytime
Stop4 Aborts the current operation of the motor. Only applies to Open / Close.
OpenMomentary5 The motor will move in the open direction: Until when the period given by the "ParameterMaximumTime" parameter has expired Stops motor if the same state is set again. This state is applicable only for Din2Mc2.
CloseMomentary6 The motor will move in the close direction: Until when the period given by the "ParameterMaximumTime" parameter has expired Stops motor if the same state is set again. This state is applicable only for Din2Mc2.
OpenMomentaryFull7 The motor will move in open direction: If the motor is set to this state and is in this state for more than 0.5 seconds, then the motor will behavior will as if it is set to OpenMomentary state. If the motor is in this state and same state is set again within 0.5 seconds the motor behavior will be like as if it is set to Open state. During the movement to the full open position if OpenMomentaryFull state is again set twice within 0.5 seconds then motor will be stopped. This state is applicable only for Din2Mc2.
CloseMomentaryFull8 The motor will move in close direction: If the motor is set to this state and is in this state for more than 0.5 seconds, then the motor will behavior will as if it is set to CloseMomentary state. If the motor is in this state and same state is set again within 0.5 seconds the motor behavior will be like as if it is set to Close state. During the movement to the full close position if OpenMomentaryFull state is again set twice within 0.5 seconds then motor will be stopped. This state is applicable only for Din2Mc2.
OpenStopCloseStop9 Cycles between the Open, Stop, Close and Stop states. If the motor is stopped for some reason other than by setting this state again, e.g., the mechanical limit is reached, or another state is set, and later this state set the motor will move in the opposite direction. This state is applicable only for Din2Mc2.