| Member name | Value | Description |
|---|
| Off | 0 |
The lamp shall be extinguished immediately without fading.
|
| Up | 1 |
Dim up 200 ms using the selected FADE RATE. During fading bit 4 on the status register shall indicate a “fade is running”.
There shall be no change if the arc power level is already at the "MAX LEVEL".
|
| Down | 2 |
Dim down 200 ms using the selected FADE RATE. During fading bit 4 on the status register shall indicate a “fade is running”.
There shall be no change if the arc power level is already at the "MIN LEVEL".
|
| StepUp | 3 |
The actual arc power level shall be set one step higher immediately without fading.
There shall be no change if the arc power level is already at the "MAX LEVEL".
|
| StepDown | 4 |
The actual arc power level shall be set one step lower immediately without fading.
There shall be no change if the arc power level is already at the "MIN LEVEL".
|
| RecallMaximumLevel | 5 |
The actual arc power level shall be set to the "MAX LEVEL" without fading. If the lamp is off it
shall be switched on with this command.
|
| RecallMinimumLevel | 6 |
The actual arc power level shall be set to the "MIN LEVEL" without fading. If the lamp is off it
shall be switched on with this command.
|
| StepDownAndOff | 7 |
The actual arc power level shall be set one step lower immediately without fading.
If the actual arc power level is already at the "MIN LEVEL", the lamp shall be switched off by
this command.
|
| OnAndStepUp | 8 |
The actual arc power level shall be set one step higher immediately without fading.
If the lamp is switched off, the lamp shall be switched on with this command and shall be set
to the "MIN LEVEL".
|
| GoToScene0 | 16 |
Set the actual arc power level to the value stored for scene 0 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene1 | 17 |
Set the actual arc power level to the value stored for scene 1 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene2 | 18 |
Set the actual arc power level to the value stored for scene 2 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene3 | 19 |
Set the actual arc power level to the value stored for scene 3 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene4 | 20 |
Set the actual arc power level to the value stored for scene 4 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene5 | 21 |
Set the actual arc power level to the value stored for scene 5 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene6 | 22 |
Set the actual arc power level to the value stored for scene 6 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene7 | 23 |
Set the actual arc power level to the value stored for scene 7 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene8 | 24 |
Set the actual arc power level to the value stored for scene 8 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene9 | 25 |
Set the actual arc power level to the value stored for scene 9 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene10 | 26 |
Set the actual arc power level to the value stored for scene 10 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene11 | 27 |
Set the actual arc power level to the value stored for scene 11 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene12 | 28 |
Set the actual arc power level to the value stored for scene 12 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene13 | 29 |
Set the actual arc power level to the value stored for scene 13 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene14 | 30 |
Set the actual arc power level to the value stored for scene 14 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| GoToScene15 | 31 |
Set the actual arc power level to the value stored for scene 15 using the actual fade time.
During fading, bit 4 on the status register shall indicate a "fade is running".
|
| Reset | 32 |
Configuration commands
|
| StoreActualLevelInTheDtr | 33 |
The actual arc power level shall be stored in the DTR.
In case of a lamp failure the "virtual” Arc Power Level shall be stored.
|
| StoreDtrAsMaximumLevel | 42 |
The value in "Data Transfer Register" shall be saved as the new "MAX LEVEL".
|
| StoreDtrAsMinimumLevel | 43 |
The value in "Data Transfer Register" shall be stored as new "MIN LEVEL".
|
| StoreDtrAsSystemFailureLevel | 44 |
The value in "Data Transfer Register" shall be saved as new "SYSTEM FAILURE LEVEL".
|
| StoreDtrAsPowerOnLevel | 45 |
The value in "Data Transfer Register" shall be saved as the new "POWER ON LEVEL".
|
| StoreDtrAsFadeTime | 46 |
Store the DTR value as Fade Time. The new fade time shall be valid after the reception of the next arc power command.
|
| StoreDtrAsScene6 | 46 |
The value in the Data Transfer Register shall be stored as a new level for the scene 6.
|
| StoreDtrAsFadeRate | 47 |
Store the DTR value as Fade Rate. The new fade rate shall be valid after the reception of the next arc power command.
|
| StoreDtrAsScene0 | 64 |
The value in the Data Transfer Register shall be stored as a new level for the scene 0.
|
| StoreDtrAsScene1 | 65 |
The value in the Data Transfer Register shall be stored as a new level for the scene 1.
|
| StoreDtrAsScene2 | 66 |
The value in the Data Transfer Register shall be stored as a new level for the scene 2.
|
| StoreDtrAsScene3 | 67 |
The value in the Data Transfer Register shall be stored as a new level for the scene 3.
|
| StoreDtrAsScene4 | 68 |
The value in the Data Transfer Register shall be stored as a new level for the scene 4.
|
| StoreDtrAsScene5 | 69 |
The value in the Data Transfer Register shall be stored as a new level for the scene 5.
|
| StoreDtrAsScene7 | 71 |
The value in the Data Transfer Register shall be stored as a new level for the scene 7.
|
| StoreDtrAsScene8 | 72 |
The value in the Data Transfer Register shall be stored as a new level for the scene 8.
|
| StoreDtrAsScene9 | 73 |
The value in the Data Transfer Register shall be stored as a new level for the scene 9.
|
| StoreDtrAsScene10 | 74 |
The value in the Data Transfer Register shall be stored as a new level for the scene 10.
|
| StoreDtrAsScene11 | 75 |
The value in the Data Transfer Register shall be stored as a new level for the scene 11.
|
| StoreDtrAsScene12 | 76 |
The value in the Data Transfer Register shall be stored as a new level for the scene 12.
|
| StoreDtrAsScene13 | 77 |
The value in the Data Transfer Register shall be stored as a new level for the scene 13.
|
| StoreDtrAsScene14 | 78 |
The value in the Data Transfer Register shall be stored as a new level for the scene 14.
|
| StoreDtrAsScene15 | 79 |
The value in the Data Transfer Register shall be stored as a new level for the scene 15.
|
| RemoveFromScene0 | 80 |
The control gear shall be removed from scene 0.
|
| RemoveFromScene1 | 81 |
The control gear shall be removed from scene 1.
|
| RemoveFromScene2 | 82 |
The control gear shall be removed from scene 2.
|
| RemoveFromScene3 | 83 |
The control gear shall be removed from scene 3.
|
| RemoveFromScene4 | 84 |
The control gear shall be removed from scene 4.
|
| RemoveFromScene5 | 85 |
The control gear shall be removed from scene 5.
|
| RemoveFromScene6 | 86 |
The control gear shall be removed from scene 6.
|
| RemoveFromScene7 | 87 |
The control gear shall be removed from scene 7.
|
| RemoveFromScene8 | 88 |
The control gear shall be removed from scene 8.
|
| RemoveFromScene9 | 89 |
The control gear shall be removed from scene 9.
|
| RemoveFromScene10 | 90 |
The control gear shall be removed from scene 10.
|
| RemoveFromScene11 | 91 |
The control gear shall be removed from scene 11.
|
| RemoveFromScene12 | 92 |
The control gear shall be removed from scene 12.
|
| RemoveFromScene13 | 93 |
The control gear shall be removed from scene 13.
|
| RemoveFromScene14 | 94 |
The control gear shall be removed from scene 14.
|
| RemoveFromScene15 | 95 |
The control gear shall be removed from scene 15.
|
| AddToGroup0 | 96 |
The control gear shall be added to group 0.
|
| AddToGroup1 | 97 |
The control gear shall be added to group 1.
|
| AddToGroup2 | 98 |
The control gear shall be added to group 2.
|
| AddToGroup3 | 99 |
The control gear shall be added to group 3.
|
| AddToGroup4 | 100 |
The control gear shall be added to group 4.
|
| AddToGroup5 | 101 |
The control gear shall be added to group 5.
|
| AddToGroup6 | 102 |
The control gear shall be added to group 6.
|
| AddToGroup7 | 103 |
The control gear shall be added to group 7.
|
| AddToGroup8 | 104 |
The control gear shall be added to group 8.
|
| AddToGroup9 | 105 |
The control gear shall be added to group 9.
|
| AddToGroup10 | 106 |
The control gear shall be added to group 10.
|
| AddToGroup11 | 107 |
The control gear shall be added to group 11.
|
| AddToGroup12 | 108 |
The control gear shall be added to group 12.
|
| AddToGroup13 | 109 |
The control gear shall be added to group 13.
|
| AddToGroup14 | 110 |
The control gear shall be added to group 14.
|
| AddToGroup15 | 111 |
The control gear shall be added to group 15.
|
| RemoveFromGroup0 | 112 |
The control gear shall be removed from group 0.
|
| RemoveFromGroup1 | 113 |
The control gear shall be removed from group 1.
|
| RemoveFromGroup2 | 114 |
The control gear shall be removed from group 2.
|
| RemoveFromGroup3 | 115 |
The control gear shall be removed from group 3.
|
| RemoveFromGroup4 | 116 |
The control gear shall be removed from group 4.
|
| RemoveFromGroup5 | 117 |
The control gear shall be removed from group 5.
|
| RemoveFromGroup6 | 118 |
The control gear shall be removed from group 6.
|
| RemoveFromGroup7 | 119 |
The control gear shall be removed from group 7.
|
| RemoveFromGroup8 | 120 |
The control gear shall be removed from group 8.
|
| RemoveFromGroup9 | 121 |
The control gear shall be removed from group 9.
|
| RemoveFromGroup10 | 122 |
The control gear shall be removed from group 10.
|
| RemoveFromGroup11 | 123 |
The control gear shall be removed from group 11.
|
| RemoveFromGroup12 | 124 |
The control gear shall be removed from group 12.
|
| RemoveFromGroup13 | 125 |
The control gear shall be removed from group 13.
|
| RemoveFromGroup14 | 126 |
The control gear shall be removed from group 14.
|
| RemoveFromGroup15 | 127 |
The control gear shall be removed from group 15.
|
| StoreDtrAsShortAddress | 128 |
The value in the DTR shall be saved as a new short address.
|
| QueryStatus | 144 |
Query commands
|
| QueryBallast | 145 |
Ask if there is a control gear with the given address that is able to communicate. The answer
shall be "Yes" or "No".
|
| QueryLampFailure | 146 |
Ask if there is a lamp problem at the given address. The answer shall be "Yes" or "No".
|
| QueryLampPowerOn | 147 |
Ask if there is a lamp operating at the given address. The answer shall be "Yes" or "No".
|
| QueryLimitError | 148 |
Ask if the last requested arc power level at the given address could not be met, because it is
above the MAX LEVEL or below the MIN LEVEL. The answer shall be "Yes" or "No".
|
| QueryResetState | 149 |
Ask if the control gear is in "RESET STATE". The answer shall be "Yes" or "No".
|
| QueryMissingStartAddress | 150 |
Ask if the control gear has no short address. The answer shall be "Yes" or "No".
The answer shall be "Yes" if the control gear has no short address.
|
| QueryVersionNumber | 151 |
Query the Version Number of the control gear. The answer shall be 1.
|
| QueryContentDtr | 152 |
Query the DTR content of the control gear. The answer shall be the content of the DTR as an 8-bit number.
|
| QueryDeviceType | 153 |
Query the device type of the control gear. The answer shall be the device type as an 8-bit number. If the control gear supports more
than one device type the answer shall be 255 (“MASK”).
|
| QueryPhysicalMinimumLevel | 154 |
Query the physical minimum level. The answer shall be the "PHYSICAL MINIMUM LEVEL" as an 8-bit number.
|
| QueryPowerFailure | 155 |
The answer shall be "YES" if the control gear has not received a "RESET" or one of the
following arc power control commands since the last power-on: "DIRECT ARC POWER
CONTROL", "OFF", "RECALL MAX LEVEL", "RECALL MIN LEVEL", "STEP DOWN AND
OFF", "ON AND STEP UP", "GO TO SCENE"
|
| QueryActualLevel | 160 |
Query the arc power level of the control gear. The answer shall be the actual arc power level. During preheating and whenever there is a
lamp error the answer shall be "MASK".
|
| QueryMaximumLevel | 161 |
Query the maximum arc power level of the control gear. The answer shall be this level as an 8-bit number.
|
| QueryMinimumLevel | 162 |
Query the minimum arc power level of the control gear. The answer shall be this level as an 8-bit number.
|
| QueryPowerOnLevel | 163 |
Query the power on level of control gear. The answer shall be this level as an 8-bit number.
|
| QuerySystemFailureLevel | 164 |
Query the system failure level of the control gear. The answer shall be this level as an 8-bit number.
|
| QueryFadeTimeOrFadeRate | 165 |
Query the Fade Time/Rate of the control gear. The answer shall be XXXX YYYY, where XXXX is the fade time and YYYY is the fade rate.
|
| QueryScene0Level | 176 |
Query the Scene 0 level of the control gear. The answer shall be the arc power level of scene 0 as an 8-bit number.
|
| QueryScene1Level | 177 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 1 as an 8-bit number.
|
| QueryScene2Level | 178 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 2 as an 8-bit number.
|
| QueryScene3Level | 179 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 3 as an 8-bit number.
|
| QueryScene4Level | 180 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 4 as an 8-bit number.
|
| QueryScene5Level | 181 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 5 as an 8-bit number.
|
| QueryScene6Level | 182 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 6 as an 8-bit number.
|
| QueryScene7Level | 183 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 7 as an 8-bit number.
|
| QueryScene8Level | 184 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 8 as an 8-bit number.
|
| QueryScene9Level | 185 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 9 as an 8-bit number.
|
| QueryScene10Level | 186 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 10 as an 8-bit number.
|
| QueryScene11Level | 187 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 11 as an 8-bit number.
|
| QueryScene12Level | 188 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 12 as an 8-bit number.
|
| QueryScene13Level | 189 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 13 as an 8-bit number.
|
| QueryScene14Level | 190 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 14 as an 8-bit number.
|
| QueryScene15Level | 191 |
Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 15 as an 8-bit number.
|
| QueryGroups0To7 | 192 |
Query to know if the control gear belongs to any of the groups 0-7. An 8-bit pattern indicating which group (0-7) the control gear belongs to is returned.
|
| QueryGroups8To15 | 193 |
Query to know if the control gear belongs to any of the groups 8-15. An 8-bit pattern indicating which group (8-15) the control gear belongs to is returned.
|
| QueryRandomAddressHigh | 194 |
Query Random Address High Byte of the control gear.
|
| QueryRandomAddressMedium | 195 |
Query Random Address Middle Byte of the control gear.
|
| QueryRandomAddressLow | 196 |
Query Random Address Low Byte of the control gear.
|