DaliLoopeTwoByteCommandCodes Enumeration

Enum to define DALI 2-byte Command codes. Based on the address provided for the command the command will be sent to DaliBallast/DaliGroup/All Ballasts. For Direct Arc Power Control command the arc power level shall be provided in place of the command code. Refer the DALI specification "IEC 62386-102 Digital addressable Lighting Interface_General Requirements-Control Gear.pdf" for more details on the following commands.

Namespace: Crestron.SimplSharpPro.Lighting
Assembly: Crestron.SimplSharpPro.Lighting (in Crestron.SimplSharpPro.Lighting.dll) Version: 2.21.121
Syntax
C#
public enum eTwoByteCommandCodes
Members
Member nameValueDescription
Off0 The lamp shall be extinguished immediately without fading.
Up1 Dim up 200 ms using the selected FADE RATE. During fading bit 4 on the status register shall indicate a “fade is running”. There shall be no change if the arc power level is already at the "MAX LEVEL".
Down2 Dim down 200 ms using the selected FADE RATE. During fading bit 4 on the status register shall indicate a “fade is running”. There shall be no change if the arc power level is already at the "MIN LEVEL".
StepUp3 The actual arc power level shall be set one step higher immediately without fading. There shall be no change if the arc power level is already at the "MAX LEVEL".
StepDown4 The actual arc power level shall be set one step lower immediately without fading. There shall be no change if the arc power level is already at the "MIN LEVEL".
RecallMaximumLevel5 The actual arc power level shall be set to the "MAX LEVEL" without fading. If the lamp is off it shall be switched on with this command.
RecallMinimumLevel6 The actual arc power level shall be set to the "MIN LEVEL" without fading. If the lamp is off it shall be switched on with this command.
StepDownAndOff7 The actual arc power level shall be set one step lower immediately without fading. If the actual arc power level is already at the "MIN LEVEL", the lamp shall be switched off by this command.
OnAndStepUp8 The actual arc power level shall be set one step higher immediately without fading. If the lamp is switched off, the lamp shall be switched on with this command and shall be set to the "MIN LEVEL".
GoToScene016 Set the actual arc power level to the value stored for scene 0 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene117 Set the actual arc power level to the value stored for scene 1 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene218 Set the actual arc power level to the value stored for scene 2 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene319 Set the actual arc power level to the value stored for scene 3 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene420 Set the actual arc power level to the value stored for scene 4 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene521 Set the actual arc power level to the value stored for scene 5 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene622 Set the actual arc power level to the value stored for scene 6 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene723 Set the actual arc power level to the value stored for scene 7 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene824 Set the actual arc power level to the value stored for scene 8 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene925 Set the actual arc power level to the value stored for scene 9 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1026 Set the actual arc power level to the value stored for scene 10 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1127 Set the actual arc power level to the value stored for scene 11 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1228 Set the actual arc power level to the value stored for scene 12 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1329 Set the actual arc power level to the value stored for scene 13 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1430 Set the actual arc power level to the value stored for scene 14 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
GoToScene1531 Set the actual arc power level to the value stored for scene 15 using the actual fade time. During fading, bit 4 on the status register shall indicate a "fade is running".
Reset32 Configuration commands
StoreActualLevelInTheDtr33 The actual arc power level shall be stored in the DTR. In case of a lamp failure the "virtual” Arc Power Level shall be stored.
StoreDtrAsMaximumLevel42 The value in "Data Transfer Register" shall be saved as the new "MAX LEVEL".
StoreDtrAsMinimumLevel43 The value in "Data Transfer Register" shall be stored as new "MIN LEVEL".
StoreDtrAsSystemFailureLevel44 The value in "Data Transfer Register" shall be saved as new "SYSTEM FAILURE LEVEL".
StoreDtrAsPowerOnLevel45 The value in "Data Transfer Register" shall be saved as the new "POWER ON LEVEL".
StoreDtrAsFadeTime46 Store the DTR value as Fade Time. The new fade time shall be valid after the reception of the next arc power command.
StoreDtrAsScene646 The value in the Data Transfer Register shall be stored as a new level for the scene 6.
StoreDtrAsFadeRate47 Store the DTR value as Fade Rate. The new fade rate shall be valid after the reception of the next arc power command.
StoreDtrAsScene064 The value in the Data Transfer Register shall be stored as a new level for the scene 0.
StoreDtrAsScene165 The value in the Data Transfer Register shall be stored as a new level for the scene 1.
StoreDtrAsScene266 The value in the Data Transfer Register shall be stored as a new level for the scene 2.
StoreDtrAsScene367 The value in the Data Transfer Register shall be stored as a new level for the scene 3.
StoreDtrAsScene468 The value in the Data Transfer Register shall be stored as a new level for the scene 4.
StoreDtrAsScene569 The value in the Data Transfer Register shall be stored as a new level for the scene 5.
StoreDtrAsScene771 The value in the Data Transfer Register shall be stored as a new level for the scene 7.
StoreDtrAsScene872 The value in the Data Transfer Register shall be stored as a new level for the scene 8.
StoreDtrAsScene973 The value in the Data Transfer Register shall be stored as a new level for the scene 9.
StoreDtrAsScene1074 The value in the Data Transfer Register shall be stored as a new level for the scene 10.
StoreDtrAsScene1175 The value in the Data Transfer Register shall be stored as a new level for the scene 11.
StoreDtrAsScene1276 The value in the Data Transfer Register shall be stored as a new level for the scene 12.
StoreDtrAsScene1377 The value in the Data Transfer Register shall be stored as a new level for the scene 13.
StoreDtrAsScene1478 The value in the Data Transfer Register shall be stored as a new level for the scene 14.
StoreDtrAsScene1579 The value in the Data Transfer Register shall be stored as a new level for the scene 15.
RemoveFromScene080 The control gear shall be removed from scene 0.
RemoveFromScene181 The control gear shall be removed from scene 1.
RemoveFromScene282 The control gear shall be removed from scene 2.
RemoveFromScene383 The control gear shall be removed from scene 3.
RemoveFromScene484 The control gear shall be removed from scene 4.
RemoveFromScene585 The control gear shall be removed from scene 5.
RemoveFromScene686 The control gear shall be removed from scene 6.
RemoveFromScene787 The control gear shall be removed from scene 7.
RemoveFromScene888 The control gear shall be removed from scene 8.
RemoveFromScene989 The control gear shall be removed from scene 9.
RemoveFromScene1090 The control gear shall be removed from scene 10.
RemoveFromScene1191 The control gear shall be removed from scene 11.
RemoveFromScene1292 The control gear shall be removed from scene 12.
RemoveFromScene1393 The control gear shall be removed from scene 13.
RemoveFromScene1494 The control gear shall be removed from scene 14.
RemoveFromScene1595 The control gear shall be removed from scene 15.
AddToGroup096 The control gear shall be added to group 0.
AddToGroup197 The control gear shall be added to group 1.
AddToGroup298 The control gear shall be added to group 2.
AddToGroup399 The control gear shall be added to group 3.
AddToGroup4100 The control gear shall be added to group 4.
AddToGroup5101 The control gear shall be added to group 5.
AddToGroup6102 The control gear shall be added to group 6.
AddToGroup7103 The control gear shall be added to group 7.
AddToGroup8104 The control gear shall be added to group 8.
AddToGroup9105 The control gear shall be added to group 9.
AddToGroup10106 The control gear shall be added to group 10.
AddToGroup11107 The control gear shall be added to group 11.
AddToGroup12108 The control gear shall be added to group 12.
AddToGroup13109 The control gear shall be added to group 13.
AddToGroup14110 The control gear shall be added to group 14.
AddToGroup15111 The control gear shall be added to group 15.
RemoveFromGroup0112 The control gear shall be removed from group 0.
RemoveFromGroup1113 The control gear shall be removed from group 1.
RemoveFromGroup2114 The control gear shall be removed from group 2.
RemoveFromGroup3115 The control gear shall be removed from group 3.
RemoveFromGroup4116 The control gear shall be removed from group 4.
RemoveFromGroup5117 The control gear shall be removed from group 5.
RemoveFromGroup6118 The control gear shall be removed from group 6.
RemoveFromGroup7119 The control gear shall be removed from group 7.
RemoveFromGroup8120 The control gear shall be removed from group 8.
RemoveFromGroup9121 The control gear shall be removed from group 9.
RemoveFromGroup10122 The control gear shall be removed from group 10.
RemoveFromGroup11123 The control gear shall be removed from group 11.
RemoveFromGroup12124 The control gear shall be removed from group 12.
RemoveFromGroup13125 The control gear shall be removed from group 13.
RemoveFromGroup14126 The control gear shall be removed from group 14.
RemoveFromGroup15127 The control gear shall be removed from group 15.
StoreDtrAsShortAddress128 The value in the DTR shall be saved as a new short address.
QueryStatus144 Query commands
QueryBallast145 Ask if there is a control gear with the given address that is able to communicate. The answer shall be "Yes" or "No".
QueryLampFailure146 Ask if there is a lamp problem at the given address. The answer shall be "Yes" or "No".
QueryLampPowerOn147 Ask if there is a lamp operating at the given address. The answer shall be "Yes" or "No".
QueryLimitError148 Ask if the last requested arc power level at the given address could not be met, because it is above the MAX LEVEL or below the MIN LEVEL. The answer shall be "Yes" or "No".
QueryResetState149 Ask if the control gear is in "RESET STATE". The answer shall be "Yes" or "No".
QueryMissingStartAddress150 Ask if the control gear has no short address. The answer shall be "Yes" or "No". The answer shall be "Yes" if the control gear has no short address.
QueryVersionNumber151 Query the Version Number of the control gear. The answer shall be 1.
QueryContentDtr152 Query the DTR content of the control gear. The answer shall be the content of the DTR as an 8-bit number.
QueryDeviceType153 Query the device type of the control gear. The answer shall be the device type as an 8-bit number. If the control gear supports more than one device type the answer shall be 255 (“MASK”).
QueryPhysicalMinimumLevel154 Query the physical minimum level. The answer shall be the "PHYSICAL MINIMUM LEVEL" as an 8-bit number.
QueryPowerFailure155 The answer shall be "YES" if the control gear has not received a "RESET" or one of the following arc power control commands since the last power-on: "DIRECT ARC POWER CONTROL", "OFF", "RECALL MAX LEVEL", "RECALL MIN LEVEL", "STEP DOWN AND OFF", "ON AND STEP UP", "GO TO SCENE"
QueryActualLevel160 Query the arc power level of the control gear. The answer shall be the actual arc power level. During preheating and whenever there is a lamp error the answer shall be "MASK".
QueryMaximumLevel161 Query the maximum arc power level of the control gear. The answer shall be this level as an 8-bit number.
QueryMinimumLevel162 Query the minimum arc power level of the control gear. The answer shall be this level as an 8-bit number.
QueryPowerOnLevel163 Query the power on level of control gear. The answer shall be this level as an 8-bit number.
QuerySystemFailureLevel164 Query the system failure level of the control gear. The answer shall be this level as an 8-bit number.
QueryFadeTimeOrFadeRate165 Query the Fade Time/Rate of the control gear. The answer shall be XXXX YYYY, where XXXX is the fade time and YYYY is the fade rate.
QueryScene0Level176 Query the Scene 0 level of the control gear. The answer shall be the arc power level of scene 0 as an 8-bit number.
QueryScene1Level177 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 1 as an 8-bit number.
QueryScene2Level178 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 2 as an 8-bit number.
QueryScene3Level179 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 3 as an 8-bit number.
QueryScene4Level180 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 4 as an 8-bit number.
QueryScene5Level181 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 5 as an 8-bit number.
QueryScene6Level182 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 6 as an 8-bit number.
QueryScene7Level183 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 7 as an 8-bit number.
QueryScene8Level184 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 8 as an 8-bit number.
QueryScene9Level185 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 9 as an 8-bit number.
QueryScene10Level186 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 10 as an 8-bit number.
QueryScene11Level187 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 11 as an 8-bit number.
QueryScene12Level188 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 12 as an 8-bit number.
QueryScene13Level189 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 13 as an 8-bit number.
QueryScene14Level190 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 14 as an 8-bit number.
QueryScene15Level191 Query the Scene 1 level of the control gear. The answer shall be the arc power level of scene 15 as an 8-bit number.
QueryGroups0To7192 Query to know if the control gear belongs to any of the groups 0-7. An 8-bit pattern indicating which group (0-7) the control gear belongs to is returned.
QueryGroups8To15193 Query to know if the control gear belongs to any of the groups 8-15. An 8-bit pattern indicating which group (8-15) the control gear belongs to is returned.
QueryRandomAddressHigh194 Query Random Address High Byte of the control gear.
QueryRandomAddressMedium195 Query Random Address Middle Byte of the control gear.
QueryRandomAddressLow196 Query Random Address Low Byte of the control gear.