DaliLoopeCommonControlCommandCodes Enumeration

Enum to define DALI 3-byte Common Control Command Codes.

Namespace: Crestron.SimplSharpPro.Lighting
Assembly: Crestron.SimplSharpPro.Lighting (in Crestron.SimplSharpPro.Lighting.dll) Version: 2.21.121
Syntax
C#
public enum eCommonControlCommandCodes
Members
Member nameValueDescription
QueryData0 Used to read data specified by the 3rd byte.
QueryFeatureSupport1 Used to determine if a feature is supported or not.
SetDtrX2 Used to set the DTR X register.
SetDtrY3 Used to set the DTR Y register.
SaveDataAtDtr4 Store "data" into memory location specified by DTR X/Y.
ReadValueFromLocation5 Read memory location specified by DTR X. Use "data" as second pointer.
AndDataIntoMemoryLocation6 "data" lists bits to clear in the memory location pointed by DTR X/Y.
OrDataIntoMemoryLocation7 "data" lists bits to set in the memory location pointed by DTR X/Y.
SetCg0GroupAssignmentForGroups0To78 "data" bits set '1' to join each desired group (groups 0-7).
SetCg1GroupAssignmentForGroups8To159 "data" bits set '1' to join each desired group (groups 8-15).
SetCg2GroupAssignmentForGroups16To2310 "data" bits set '1' to join each desired group (groups 16-23).
SetCg3GroupAssignmentForGroups24To3111 "data" bits set '1' to join each desired group (groups 24-31).
SetPbo12 Bank "0" is "normal operation", bank 1 is e.g. "after hours" operation if supported.
SetPbrw13 "data" specifies the bank being written/read to/from.
DataLessCommandContainedInData14 Dataless command contained in data.
RestoreFactoryDefault15 "data" sets upper limit. All registers below or equal are reset to default values.
SetOba0TwoByteControlOutputAByte115 Beginning Of Parameter Bank
SetOba1TwoByteControlOutputAByte216 "data" contains second byte of inactive to active output A byte (ballast/actuator).
SetObb0TwoByteControlOutputBByte117 "data" contains first byte of inactive to active output B byte (ballast/actuator).
SetObb1TwoByteControlOutputBByte218 "data" contains second byte of inactive to active output B byte (ballast/actuator).
SetThresholdValueA19 "data" contains desired A Threshold Value.
SetThresholdValueB20 "data" contains desired B Threshold Value.
SetDelayA21 Sets Delay A 15 Seconds Value in "data".
SetDelayB22 Sets Delay B 15 Seconds Value in "data".
SetRtRepeatInterval23 If non-zero repeat sensor output every "data" 15 seconds.
SvSensorValue24 Actual sensor value sent in "data" using Controller Originator Addressing.
SetSensitivity25 Setting of Controller sensitivity/range to the value defined in "data".