Click or drag to resize

DaliLoopExecute(Byte, Byte) Method

Method to send the 2-byte DALI control/query command or special command specified by "paramAddress" (byte 1) and "paramCommandOrData" (byte 2). The commands can be sent to individual DaliBallast/DaliGroup/ all ballasts that are part of the DaliLoop.

Namespace: Crestron.SimplSharpPro.Lighting
Assembly: Crestron.SimplSharpPro.Lighting (in Crestron.SimplSharpPro.Lighting.dll) Version: 2.21.121
Syntax
C#
public void Execute(
	byte paramAddress,
	byte paramCommandOrData
)

Parameters

paramAddress  Byte
The address portion (byte 1) of the 2-byte DALI control/query command or special command.
paramCommandOrData  Byte
The command portion (byte 2) of the 2-byte DALI control/query or special command.
Remarks
Command numbers from 256 to 272 are special commands. Address formats are as follows... Short or group address: YAAA AAAS Short addresses 0 through 63: 0AAA AAAS Group addresses 0 through 15: 100A AAAS Broadcast: 1111 111S Special commands (broadcast): 101C CCC1 or 110C CCC1 Where A is the significant address bit; S is the selector bit (0 = direct arc power level following; 1 = command following); C is the significant "SPECIAL COMMAND"; and Y is the address specifier (0 = short address; 1 - group address or broadcast)

Version Information

.NET

Supported in: 6.0