DaliLoopExecute(Byte, Byte) Method |
Method to send the 2-byte DALI control/query command or special command specified by "paramAddress"
(byte 1) and "paramCommandOrData" (byte 2). The commands can be sent to individual
DaliBallast/
DaliGroup/
all
ballasts that are part of the
DaliLoop.
Namespace: Crestron.SimplSharpPro.LightingAssembly: Crestron.SimplSharpPro.Lighting (in Crestron.SimplSharpPro.Lighting.dll) Version: 2.21.121
Syntaxpublic void Execute(
byte paramAddress,
byte paramCommandOrData
)
Parameters
- paramAddress Byte
- The address portion (byte 1) of the 2-byte DALI control/query command or special command.
- paramCommandOrData Byte
- The command portion (byte 2) of the 2-byte DALI control/query or special command.
RemarksCommand numbers from 256 to 272 are special commands.
Address formats are as follows...
Short or group address: YAAA AAAS
Short addresses 0 through 63: 0AAA AAAS
Group addresses 0 through 15: 100A AAAS
Broadcast: 1111 111S
Special commands (broadcast): 101C CCC1 or 110C CCC1
Where A is the significant address bit;
S is the selector bit (0 = direct arc power level following; 1 = command following);
C is the significant "SPECIAL COMMAND"; and
Y is the address specifier (0 = short address; 1 - group address or broadcast)
Version Information
.NET
Supported in: 6.0
.NET Compact Framework
Supported in: 3.5
See Also