 NameDescription
Public propertyAuto1ptSetpoint Sets the auto1pt setpoint, where 1d = 0.1 degrees. The value is based on the current temperature scale (Fahrenheit or Celsius). The displayed value is rounded to whole or half degrees based on the setting.
Public propertyAuto1ptSetpointFeedback Reports the active auto1pt setpoint value. This output should be connected to the corresponding setpoint input; otherwise the output will not report the setpoint value.

The BaseEvent event will trigger with Auto1ptSetpointFeedbackEventId.

Public propertyAutoDeadbandFeedback Reports the auto deadband value selected via the "db" option in the Setup menu, where 1d = 0.1 degrees. In dual-setpoint auto mode, this value is the minimum separation between heat and cool setpoints, which prevents the system from toggling back and forth due to overshoot. In single-setpoint auto mode, this value sets the hysteresis used when changing from heat to cool. For example, if the setpoint is 70°F with auto deadband of 2 degrees, the temperature would have to rise to 72°F before running cool, and 68°F before running heat. HZ-THSTAT reports auto mode deadband parameter in 10ths of current unit: Fahrenheit : 20, 30, 40, 50, 60 (F). Celsius : 10, 20, 30 (C).

The BaseEvent event will trigger with AutoDeadbandFeedbackEventId.

Public propertyConnectedIpList A property containing the list of the ConnectedIpInformation objects which contain information about the devices that are connected to this IP ID. This property is only valid for an ethernet device. If this is not an ethernet device, then this property will return null. If this is an ethernet device, the list will be non-null. It will be empty if no devices are connected. The order of items in this list is not guaranteed.
(Inherited from GenericDevice)
Public propertyCoolCallFeedbacks Returns a collection of components that indicate when the system is calling for cooling.

The ClimateControlComponentCallChange event will trigger with ClimateControlComponent object.

Public propertyCoolSetpoint Sets the cool setpoint, where 1d = 0.1 degrees. The value is based on the current temperature scale (Fahrenheit or Celsius). The displayed value is rounded to whole or half degrees based on the setting.
Public propertyCoolSetpointFeedback Reports the active cool setpoint value. This output should be connected to the corresponding setpoint input; otherwise the output will not report the setpoint value.

The BaseEvent event will trigger with CoolSetpointFeedbackEventId.

Public propertyCode exampleDescription Get/Set the description of this device.
(Inherited from GenericBase)
Public propertyDisposed Property to indicate if the device has been disposed.
(Inherited from GenericDevice)
Public propertyHeatCallFeedbacks Returns a collection of components that indicate when the system is calling for heat.

The ClimateControlComponentCallChange event will trigger with ClimateControlComponent object.

Public propertyHeatSetpoint Sets the heat setpoint, where 1d = 0.1 degrees. The value is based on the current temperature scale (Fahrenheit or Celsius). The displayed value is rounded to whole or half degrees based on the setting.
Public propertyHeatSetpointFeedback Reports the active heat setpoint value. This output should be connected to the corresponding setpoint input; otherwise the output will not report the setpoint value.

The BaseEvent event will trigger with HeatSetpointFeedbackEventId.

Public propertyID Property to get the ID of the device.
(Inherited from GenericDevice)
Public propertyIsOnline Property to get the current online state of the device.
(Inherited from GenericDevice)
Public propertyLocalTemperatureFeedback Reports the local temperature reported by the Local sensor. Only enabled when EnableSensorOutputs is enabled. This property is supported by "HZThstat" not supported by "DinThstat".

The TemperatureChange event will trigger with temperatureType and newTemperature.

Public propertyName Get the name of this device.
(Inherited from GenericBase)
Public propertyOutdoorTemperatureFeedback Sends the current outdoor temperature to the thermostat. This input should only be used for heatpump/dual fuel balance point systems, not heat/cool system types. The value should be sent in tenths of a degree (1d = 0.1 degrees) based on the current temperature scale (Fahrenheit or Celsius). For example, if the outdoor temperature is 45.3°F, the value should be 453.

The TemperatureChange event will trigger with temperatureType and newTemperature.

Public propertyOutdoorTemperatureInput Sends the current outdoor temperature to the thermostat. This input should only be used for heatpump/dual fuel balance point systems, not heat/cool system types. The value should be sent in tenths of a degree (1d = 0.1 degrees) based on the current temperature scale (Fahrenheit or Celsius). For example, if the outdoor temperature is 45.3°F, the value should be 453d.
Public propertyParent The parent that a given object was added to.
(Inherited from GenericBase)
Public propertyRegisterable Property to indicate that this device can be registered.
(Inherited from GenericDevice)
Public propertyRegistered Property to get the current registration state of the device.
(Inherited from GenericDevice)
Public propertyRegistrationFailureReason Property to get the Registration Failure Reason, this will match the return value from the call to register.
(Inherited from GenericDevice)
Public propertyRegulationTemperatureFeedback Reports displayed temperature, which can be the Local temperature or the Remote 1 temperature, or the average of Local and Remote 1, based on the option selected in the Setup menu (Local = i; Remote 1 = r; Average = ir).

The TemperatureChange event will trigger with temperatureType and newTemperature.

Public propertyRemote1TemperatureFeedback Reports the temperature reported by the Remote 1 sensor. Only enabled when EnableSensorOutputs is enabled.

The TemperatureChange event will trigger with temperatureType and newTemperature.

Public propertyRemote2TemperatureFeedback Reports the local temperature reported by the Remote 2 sensor. Only enabled when EnableSensorOutputs is enabled.

The TemperatureChange event will trigger with temperatureType and newTemperature.

Protected propertySIMPLDeviceImplementation Internal protected member used for actual device control.
(Inherited from GenericDevice)
Public propertyType Property to determine to type of device this is.
(Inherited from GenericDevice)
Public propertyUnRegistrationFailureReason Property to get the Unregistration Failure Reason, this will match the return value from the call to unregister.