ThermostatAutoDeadbandFeedback Property |
Reports the auto deadband value selected via the "db" option in the Setup menu, where 1d = 0.1 degrees.
In dual-setpoint auto mode, this value is the minimum separation between heat and cool setpoints,
which prevents the system from toggling back and forth due to overshoot.
In single-setpoint auto mode, this value sets the hysteresis used when changing from heat to cool.
For example, if the setpoint is 70°F with auto deadband of 2 degrees,
the temperature would have to rise to 72°F before running cool, and 68°F before running heat.
HZ-THSTAT reports auto mode deadband parameter in 10ths of current unit:
Fahrenheit : 20, 30, 40, 50, 60 (F).
Celsius : 10, 20, 30 (C).
The BaseEvent event will trigger with AutoDeadbandFeedbackEventId.