Scheduled |
The ScheduledSetpoints type exposes the following members.
| Name | Description | |
|---|---|---|
| RunSchedule | Sets the scheduler mode, which determines which events will cause the setpoint to take the value of the scheduled setpoint. 0d = The setpoint will be set to the scheduled setpoint value when: HOLD mode is exited (return to RUN mode) The System mode is changed while in RUN mode The scheduled setpoint changes while in RUN mode 1d to 65534d = The setpoint will be set to the scheduled setpoint value when: HOLD mode is exited (return to RUN mode) The System mode is changed while in RUN mode The value of RunSchedule changes | |
| ScheduledAuto1ptSetpoint | Sets the single point auto setpoint, where 1d = 0.1 degrees. | |
| ScheduledCoolSetpoint | Sets the cool auto setpoint, where 1d = 0.1 degrees. | |
| ScheduledHeatSetpoint | Sets the heat auto setpoint, where 1d = 0.1 degrees. |