The IGlsCenOcc type exposes the following members.
| Name | Description | |
|---|---|---|
| AndWhenVacatedFeedback | Property to indicate if both passive infrared (PIR) OR ultrasonic (US) sensor technologies must register motion to trigger initial room occupancy. true = motion sensed needed by both technologies for initial occupancy; false = AND logic disabled. | |
| CurrentTimeoutFeedback |
Property to indicate which timeout is being used by the sensor.
The BaseEvent event will trigger with: GlsOccupancySensorBase.TimeoutFeedbackEventId for GlsOccupancySensorBase devices; GlsOirCsmExBattEventIds.CurrentTimeoutReceivedEventId for GlsOirCsmExBatt devices. For GlppBase devices GlppBase.GlppOccupancySensorIrChange event will trigger with GlppEventIds.TimeoutFeedbackEventId. (Inherited from ICommonOccupancySensorInfo) | |
| GraceOccupancyDetectedFeedback |
Property to indicate occupancy event detected within 15s of initial vacancy event. Beyond 15s after the initial vacancy event, this property cannot be triggered.
This property is most commonly used in an application where a vacancy-only sensor is desired. In such an instance, only this property will be used to turn on the lights, while OccupancyDetectedFeedback will remain unused.
true = Occupancy event detected within 15s of initial vacancy event; false = No occupancy event detected within 15s of initial vacancy event.
The BaseEvent event will trigger with GraceOccupancyDetectedFeedbackEventId. | |
| InternalPhotoSensorValueFeedback | Property to report the internal photosensor value. The output range is from 0 to MAXIMIM VALUE TO BE DETERMINED lux, scaled linearly from 0 to 65535. | |
| LedFlashEnabledFeedback | Property to indicate if feedback LEDs are enabled or disabled that indicates if motion is detected. true = Feedback LEDs enabled; false = Feedback LEDs disabled. | |
| OccupancyDetectedFeedback |
Property to indicate occupancy status. Value is true when occupancy is detected, value is false when vacancy is detected.
The BaseEvent event will trigger with: GlsOccupancySensorBase.RoomOccupiedFeedbackEventId for GlsOccupancySensorBase devices; GlsOirCsmExBattEventIds.OccupancyStatusReceivedEventId for GlsOirCsmExBatt devices. For GlppBase devices GlppBase.GlppOccupancySensorIrChange event will trigger with GlppEventIds.RoomIsOccupiedFeedbackEventId. (Inherited from ICommonOccupancySensorInfo) | |
| OrWhenVacatedFeedback | Property to indicate if either passive infrared (PIR) OR ultrasonic (US) sensor technologies can trigger initial occupancy. true = motion sensed needed by only one technology; false = OR logic disabled. | |
| PassiveInfraredSensorEnabledFeedback | Property to report if the passive infrared (PIR) Sensor is enabled. true = PIR Sensor enabled; false = PIR Sensor disabled. | |
| PassiveInfraredSensorSensitivityInOccupiedStateFeedback | Property to report Sensitivity level for passive infrared (PIR) while sensor is in occupied state. | |
| PassiveInfraredSensorSensitivityInVacantStateFeedback | Property to report Sensitivity level for passive infrared (PIR) while sensor is in vacant state. | |
| RawOccupancyDetectedByPassiveInfraredSensorFeedback |
Property to indicate if any raw motion registered/detected by the passive infrared (PIR) sensor.
true = motion detected by passive infrared (PIR) sensor; false = No motion detected by passive infrared (PIR) sensor.
The BaseEvent event will trigger with RawOccupancyPirFeedbackEventId. | |
| RawOccupancyDetectedByUltrasonicSensorFeedback |
Property to indicate if any raw motion registered/detected by the ultrasonic (US) sensor.
true = motion detected by ultrasonic (US); false = No motion detected by ultrasonic (US).
The BaseEvent event will trigger with RawOccupancyUsFeedbackEventId. | |
| RawOccupancyDetectedFeedback |
This property value will be set to true if ultrasonic (US) AND/OR passive infrared (PIR) sensors detect motion. The AND/OR determination is decided based upon the chosen logic.
To see which logic is chosen, look at OrWhenVacatedFeedback and AndWhenVacatedFeedback.
For example, in “Vacancy AND” logic both ultrasonic (US) and passive infrared (PIR) technologies must register motion in order to set this property value to true.
true = motion detected by logical state; false = No motion detected by logical state.
The BaseEvent event will trigger with RawOccupancyFeedbackEventId. | |
| RemoteTimeout |
Property to set timeout remotely.
(Inherited from ICommonOccupancySensorInfo) | |
| ShortTimeoutEnabledFeedback | Property to report if the short timeout functionality has been enabled. true = Short timeout enabled; false = Short timeout disabled | |
| UltrasonicSensorSensitivityInOccupiedStateFeedback | Property to report Sensitivity level for ultrasonic (US) while sensor is in occupied state. | |
| UltrasonicSensorSensitivityInVacantStateFeedback | Property to report Sensitivity level for ultrasonic (US) while sensor is in vacant state. | |
| UltrasonicSensorSideAEnabledFeedback | Property to report if the ultrasonic (US) Sensor side A is enabled. | |
| UltrasonicSensorSideBEnabledFeedback | Property to report if the ultrasonic (US) Sensor side B is enabled. true = US Sensor B enabled; false = US Sensor B disabled. | |
| VacancyDetectedFeedback |
Property to indicate when the room is vacant.
"OccupancyDetectedFeedback" sets to false and VacancyDetectedFeedback sets to true.
true = Room Vacant ; false = Room Occupied.