BACnet |
The BACnetRemoteBinaryInputObject type exposes the following members.
| Name | Description | |
|---|---|---|
| CovLifetime |
Parameter to specify the default Change of Value (COV) notification lifetime in minutes. Default value is 30 minutes.
(Inherited from BACnetRemoteCommonObject) | |
| Disposed |
Property to indicate if the Device has been disposed.
(Inherited from BACnetObject) | |
| EventStateFeedback |
Property to indicate the event state associated with the object.
This property will trigger BACnetObjectChange event with EventStateFeedbackEventId. (Inherited from BACnetRemoteCommonObject) | |
| Id |
A 22-bit decimal number that serves as an unique address of the object within the BACnet device.
Valid range from 0 to 4194302.
(Inherited from BACnetObject) | |
| OutOfServiceFeedback |
Property to report whether the BACnet object is functioning as expected or not.
true means the object is out of service.
false means it is in service.
This property will trigger BACnetObjectChange event with OutOfServiceChangedEventId. (Inherited from BACnetRemoteCommonObject) | |
| Parent |
The parent that a given object was added to.
(Inherited from BACnetObject) | |
| PresentValueClearedFeedback |
Changes from false to true and again to false to indicate PresentValueFeedback is cleared (set to false).
This property will trigger BACnetObjectChange event with PresentValueClearedEventId. | |
| PresentValueFeedback |
Property to report the Present Value of the object.
This property will trigger BACnetObjectChange event with PresentValueFeedbackEventId. | |
| PresentValueSetFeedback |
Changes from false to true and again to false to indicate PresentValueFeedback is set (set to true).
This property will trigger BACnetObjectChange event with PresentValueSetEventId. | |
| Priority |
Parameter to specify the BACnet priority level at which the object will communicate.
There are 16 levels of priority, where level 1 denotes the highest priority and level 16 - the lowest.
(Inherited from BACnetRemoteCommonObject) | |
| ScanRate |
Parameter to specify the default time interval (in seconds) for polling the device properties.
This parameter will be ignored if the user chooses to set the polling interval by using the VariableScanRate.
Default value = 30s.
(Inherited from BACnetRemoteCommonObject) | |
| StatusFlagsFeedback |
Property to report the state of the four Boolean flags that indicate the general "health" of the remote object.
This property will trigger BACnetObjectChange event with StatusFlagsFeedbackEventId. (Inherited from BACnetRemoteCommonObject) | |
| SubscribeCov |
Parameter that indicates if the BACnet device subscribes to Change of Value (COV) notification.
Valid values as follows:
true = subscribes to COV notification; false = Does not subscribe COV notification
Default-value = true (subscribes to COV notification)
(Inherited from BACnetRemoteCommonObject) | |
| Type |
Type of the BACnet object.
(Inherited from BACnetObject) | |
| UserSpecifiedObject |
Can be assigned anything that user wants.
(Inherited from BACnetObject) | |
| VariableScanRate |
When non-zero, will cause the BACnet stack to poll for the value periodically.
When set to zero will poll for value at the specified interval set by the ScanRate parameter.
(Inherited from BACnetRemoteCommonObject) |