Click or drag to resize

BACnetHostAnalogValueObject Properties

The BACnetHostAnalogValueObject type exposes the following members.

Properties
 NameDescription
Public propertyCovIncrement Parameter to specify the minimum change in PresentValue that will cause change notification to be sent.
(Inherited from BACnetHostAnalogInputObject)
Public propertyDecimal Specifies the number of digits to the right of the decimal point for PresentValue or PresentValue. Valid values are as follows: 0 (indicates present value is a whole number), 1, 2, 3.
(Inherited from BACnetAnalogObject)
Public propertyDisposed Property to indicate if the Device has been disposed.
(Inherited from BACnetObject)
Public propertyId A 22-bit decimal number that serves as an unique address of the object within the BACnet device. Valid range from 0 to 4194302.
(Inherited from BACnetObject)
Public propertyName Parameter to access the name of the object. It is a printable string (restricted to maximum 80 characters in length) unique within the BACnet device.
(Inherited from BACnetAnalogObject)
Public propertyParameterUnits Parameter to specify the correct engineering units for the object. This parameter can be overridden by Units property.
(Inherited from BACnetHostAnalogInputObject)
Public propertyParent The parent that a given object was added to.
(Inherited from BACnetObject)
Public propertyPresentValue Property to report the Present Value information of the object.

This property will trigger BACnetObjectChange event with event ID PresentValueFeedbackEventId.


(Inherited from BACnetHostAnalogInputObject)
Public propertyPresentValueChangedFeedback Property to report whether there has been any change in the ValueFeedback. This property value changes from false to true and then to false whenever ValueFeedback changes.

This property will trigger BACnetObjectChange event with PresentValueChangedEventId.

Public propertyPriorityForPresentValueFeedback Indicates the write priority at which the present value is written recently by a remote device. This property is not supported on firmware with version less than "4.0003.00005" on VC4 platforms. This property is not supported on firmware with version less than "2.8004.00001" on 4-Series platform. This property is not supported on 3-Series platforms.

This property will trigger BACnetObjectChange event with event ID PriorityForPresentValueFeedbackEventId.

Public propertyRelinquish This property is the default value to be used for the ValueFeedback property when all the command priority values in the Priority Array are set to NULL. Valid value range is from 1 to 4,294,967,295.
Public propertySigned Indicates if PresentValue or PresentValue is signed or unsigned number. true = signed number; false = unsigned number. Default value is false.
(Inherited from BACnetAnalogObject)
Public propertyStatusFlags Property to report the state of the Status flags of the hosted object. Status is represented as a decimal number made of 4 bits (one for each flag).
(Inherited from BACnetHostAnalogInputObject)
Public propertyType Type of the BACnet object.
(Inherited from BACnetObject)
Public propertyUnits Property to set the correct engineering unit for PresentValue during run-time.
(Inherited from BACnetHostAnalogInputObject)
Public propertyUserSpecifiedObject Can be assigned anything that user wants.
(Inherited from BACnetObject)
Public propertyWritePriority Write priority of this object.
Top